Loading...
HomeMy WebLinkAboutCC Resolution 8171 (Unreinforced Masonry Building Program)RESOLUTION NO. 8171 A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF SAN RAFAEL ESTABLISHING ANALYSIS AND DESIGN REQUIREMENTS FOR USE WITH THE CITY'S UNREINFORCED MASONRY BUILDING MITIGATION PROGRAM WHEREAS, the San Rafael General Plan 2000 has a seismic safety element which calls for the City to implement measures to encourage the rehabilitation or elimination of structures susceptible to collapse or failure in an earthquake (Seismic Safety Policy 5-12); and WHEREAS, State law (SB 547) requires that the City Council adopt a mitigation program pertaining to existing unreinforced masonry buildings, and WHEREAS, the City Council has adopted a mitigation program pertaining to existing unreinforced masonry buildings, and WHEREAS, that program requires the City Council to adopt a resolution establishing analysis and design requirements for implementation of the City's program, and WHEREAS, the attached Exhibit "A" provides analysis and design requirements for unreinforced masonry buildings. NOW, THEREFORE, BE IT RESOLVED BY THE City Council of the City of San Rafael, that in view of the foregoing findings, the attached Exhibit "A", establishing requirements for the analysis and design of repairs to unreinforced masonry buildings, is hereby approved. I, JEANNE M. LEONCINI, Clerk of the City of San Rafael, California, hereby certify that the foregoing resolution was duly and regularly introduced and adopted at a regular meeting of the Council of said City held on the 7th day of May, 1990, by the following vote, to wit: AYES: COUNCILMEMBERS: Boro, Breiner, Thayer & Mayor Mulryan NOES: COUNCILMEMBERS: None ABSENT: COUNCILMEMBERS: Shippey JEA M. LEONCINI; City Clerk E X H I B I T "A" UNREINFORCED MASONRY BUILDING MITIGATION PROGRAM ANALYSIS AND DESIGN REQUIREMENTS SECTION I GENERAL REQUIREMENTS a) General. Every structure within the scope of Chapter 12.40 of the Municipal Code shall have a seismic resisting system conform- ing with Section 2303(b) of the Building Code, except as modified by these requirements. b) Alterations and Repairs. Alterations and repairs required to meet the provisions of these requirements shall comply with all other applicable requirements of the Building Code unless specifi- cally provided for in these requirements. c) Requirements for Plans. The following construction informa- tion shall be included in the plans required by this Chapter: 1. Accurately dimensioned floor and roof plans showing existing walls and the size and spacing of floor and roof framing members and sheathing materials. The plans shall indicate all existing and new crosswalls and their materials of construction. The location of the crosswalls and their openings shall be fully dimensioned or drawn to scale on the plans. 2. Accurately dimensioned wall elevations showing openings piers, thicknesses, and heights, wall shear test locations, cracks or damaged portions requiring repairs. The general condition of the mortar joints and if and where the joints require pointing. Where the exterior face is veneer, the type of veneer, its thickness and its bonding and/or ties to the structural wall masonry shall also be re- ported. 3. The type of interior wall and ceiling surfaces. 4. The extent and type of existing wall anchorage to floors and roof when utilized in the design. 5. The extent and type of parapet corrections which were previously performed, if any. 6. Repair details, if any, of cracked or damaged unrein- forced masonry walls required to resist forces specified in this Chapter. 7. All other plans, sections, and details necessary to delineate required retrofit construction including those items in Section IV. 1. SECTION II ALLOWABLE DESIGN VALUES a) Allowable Values. 1. Allowable values for existing materials are given in Table C and for new materials in Table D. The one-third increase in allowable values is not allowed for values in these tables. 2. Allowable values not specified in this Chapter shall be as specified elsewhere in the Building Code. Allowable values not specified in this Chapter for dead load plus seismic load may be increased 33 percent. Allowable values not specified in this Chapter for existing building elements with a combination of dead load plus floor live load plus seismic load may be increased 70 percent. 3. Minimum Acceptable Quality of Existing Unreinforced Masonry Walls. All unreinforced masonry walls utilized to carry vertical loads and seismic forces parallel and perpendicular to the wall plane shall be investigated by the licensed engineer or architect analyzing the building to determine their structural capacity. The engineer or architect shall require on site testing of existing materials where he feels such testing is necessary to analyze the building. Such testing may consist of in-place shear tests, core tests, shear bolt testing, or other test methods approved by the City. 2. SECTION III ANALYSIS AND DESIGN (a) General. Except as modified herein, the analysis and design relating to the structural alteration of existing buildings shall be in accordance with the Building Code. (b) Selection of Procedure. Buildings shall be analyzed by the General Procedure of Section III (c) which is based on Chapter 23 of the Building Code or, when applicable, buildings may be analyzed by the Special Procedure of subsection III (d). (c) General Procedure. 1. Minimum Design Lateral Forces. Buildings shall be analyzed to resist minimum lateral forces assumed to act noncurrently in the direction of each of the main axes of the structure in accordance with the following: V = 0.33ZW..................................(46-1) 2. Lateral Forces on Elements of Structures. Parts or portions of structures shall be analyzed as required in Chapter 23 of the Building Code. Exceptions: i. Unreinforced masonry walls for which height to thickness ratios do not exceed ratios set forth in Table B need not be analyzed for out -of - plane loading. Unreinforced masonry walls which exceed the allowable h/t ratios of Table B shall be braced according to Section IV (e). ii. Parapets complying with Section IV (f) need not be analyzed for out -of -plane loading. 3. Shear Walls (In -Plane Loading). Shear walls shall comply with subsection III (e). (d) Special Procedure. 1. Limits for the Application of Subsection III (d) The Special Procedure of this subsection may only be applied to buildings with the following characteristics: A. Flexible diaphragms at all levels above the base of structure. B. A maximum of 6 stories above the base of the building. 3. C. The vertical elements of the lateral force resisting system shall consist predominantly of masonry or concrete shear walls or steel braced frames or special moment resisting frames (see Section 2312 of the Building Code) each with a maximum overall height - to -length ratio of 1-1/2 to 1. D. The lateral force resisting system shall be regular as defined in the Building Code. Except for a single story building with an open front, a minimum of two lines of vertical lateral force -resisting elements shall be parallel to each axis of the building. 2. Lateral Forces on Elements of Structures. With the exception of the diaphragm provisions in subsection III (d), elements of structures shall comply with subsection III (c)2. 3. Crosswalls. Crosswalls shall meet the requirements of this subsection. A. Crosswall Definition. A crosswall is a wood -framed wall sheathed with any of the materials described in Tables or D. _ Spacing of crosswalls shall not exceed 40 feet on center measured perpendicular to the direction of consideration, and shall be placed in each story of the building. Crosswalls shall extend the full story height between diaphragms. Exception: 1. Crosswalls need not be provided at all levels in accordance with subsection III (d) 4B (iv) . 2. Existing crosswalls need not be continuous below a wood diaphragm at/or within four feet of grade provided: (i) Shear connections and anchorage requirements Section III (d)7 are satisfied at all edges of the diaphragm. (ii) Crosswalls with total shear capacity of .071:Wd interconnect the diaphragm to the foundation. (iii) The demand/capacity ratio of the diaphragm between the crosswalls that are continuous to their foundations shall be calculated as: DCR = [0.33Wd + Vca)/2vuD....... (46-2) and DCR shall not exceed 2.5. 4. B. Crosswall Shear Capacity. Within any 40 feet measured along the span of the diaphragm, the sum of the crosswall shear capacities shall be at least 30 percent of the diaphragm shear capacity of the strongest diaphragm at or above the level under consideration. C. Existing Crosswalls. Existing crosswalls shall have a length to height ratio between openings of not less than 1.5. Existing crosswall connections to diaphragms need not be investigated as long as the crosswall extends to the framing of the diaphragm above and below. D. New Crosswalls. New crosswall connections to the diaphragm shall develop the crosswall shear capacity. New Crosswalls shall have the capacity to resist an overturning moment equal to the crosswall shear capacity times the story height. Crosswall overturning moments need not be cumulative over more than two stories. E. Other Crosswall Systems. Other systems such as special moment resisting frames may be used as crosswalls provided that the yield story drift does not exceed one inch in any story. 4. Wood Diaphragms. A. Acceptable Diaphragm Span. A diaphragm is acceptable if the point (L,DCR) on Figure 1, falls within Regions 1, 2, or 3. B. Demand -Capacity Ratios. Demand -Capacity Ratios shall be calculated for the diaphragm according to the following formulas: (i) For a diaphragm without qualifying crosswalls at levels immediately above or below: DCR = O.83ZWd/7_vuD............. ............(46-3) (ii) For a diaphragm in a single -story building with qualifying crosswalls: DCR = 0.83ZWd/(7,vuD + Vcb) ...................(46-4) (iii) For diaphragms in a multi -story building with qualifying crosswalls in all levels: DCR = 0.83ZY-Wd/(7-ZvuD+Vcb)...................(46-5) DCR shall be calculated at each level for the set of diaphragms at and above the level under consideration. 5. (iv) For a roof diaphragm and the diaphragm directly below if coupled by crosswalls: DCR = 0.83Z7,Wd/JJvuD...........................(46-6) C. Chords. An analysis for diaphragm flexure need not be made and chords need not be provided. D. Collectors. An analysis shall of diaphragm collector forces shall be made for the transfer of diaphragm edge shears into vertical elements of the lateral force resisting system. Collector forces may be resisted by new or existing elements. E. Diaphragm Openings. (i) Diaphragm forces at corners of openings shall be investigated and shall be developed into the diaphragm by new or existing materials. (ii) In addition to calculating demand capacity ratios per Section III (d)4B, the demand capacity ratio of the portion of the diaphragm adjacent to an opening shall be calculated using the opening dimension as the span. (iii) Where an opening occurs in the end quarter of the diaphragm span vud for the demand capacity.ratio calculation shall be based on the net depth of the diaphragm. 5. Diaphragm Shear Transfer. Diaphragms shall be connected to shear walls with connections capable of developing a minimum force given by the lesser of the following formulas: V = 1/2ZCpWd.....................................(46-7) or V= vuD........................................(46-8) 6. Shear Walls (In Plane Loading) - Special Procedure. A. Wall Story Force. The wall story force distributed to a shear wall at any diaphragm level shall be the lesser value calculated as: (i) For buildings without crosswalls, 6. Fwx = 0.33Z(V A+Wd/2).................. ............... (46-9) but need not exceed Fwx= 0.33ZWwx + vuD................................(46-10) (ii) For buildings with crosswalls in all levels: Fwx = 0.25Z(Wwx+Sold/2).................................(46-11) but need not exceed Fwx = 0.25Z(Wwx + IWd (vuD/7-jvuD) ) ....................(46-12) and need not exceed Fwx = 0.25ZWwx + vuD..................................(46-13) B. Wall Story Shear. The wall story shear shall be the sum of the wall story forces at and above the level of consideration. Vwx= 'FFwx............................................(46-14) C. Shear Wall Analysis. Shear walls shall comply with subsection III (e). D. Moment Frames. Moment frames used in place of shear walls shall be designed as required in Chapter 23 of the Building Code except that the forces shall be as specified in Section III (d)6A and the interstory drift ratio shall be limited to 0.005. 7. Out of Plane Forces - URM Walls. A. Allowable URM Wall Height to Thickness Ratios. The provisions of Section III (c)2 are applicable except the allowable h/t ratios given in Table B . shall be determined from Figure 1_ as follows: (i) In Region 1, h/t ratios for "buildings with crosswalls" may be used if qualifying crosswalls are present in all stories. (ii) In Region 2, h/t ratios for "buildings with crosswalls" may be used whether or not qualifying crosswalls are present. (iii) In Region 3, h/t ratios for "all other buildings" shall be used whether or not qualifying crosswalls are present. 7. B. Walls -with Diaphragms in Different Regions. When diaphragms above and below the wall under consideration have DCRs in different regions of Figure 1 the lesser h/t ratio shall be used. 8. Buildings with Open Fronts. A building with an open front on one side shall have crosswalls parallel to the open front and shall be designed by the following procedure: A. Effective Diaphragm Span, Li, .for use in Figure No. 1 shall be determined in accordance with the following formula: Li = 2[(WW/Wd)•L + L) .............................(46-15) B. Diaphragm Demand/capacity ratio shall be calculated as: DCR = 0.83Z (Wd + Ww) / [ (vu D) + VC] ............... (46-16) (e). Analysis of Vertical Elements of the Lateral Force - Resisting System. Applicable to both General Procedure and Special Procedure Buildings. 1. Existing URM Walls. A. Flexural Rigidity. Flexural rigidity may be neglected in determining the rigidity of an URM wall. B. Shear Walls with Openings. Wall piers shall be analyzed according to the following procedure: (i) For any pier, (1) The pier shear capacity shall be calculated as: Va = vaDt......................... ...(46-17) (2) The pier rocking shear capacity shall be calculated as: Vr = 0.5PDD/H...........................(46-18) (ii) The wall piers at any level are acceptable if they comply with one of the following modes of behavior: (1) Rocking Mode. Where all piers at a level have shear capacities capable of sustaining rocking, i.e., the pier shear capacity is greater than or equal to the pier rocking shear capacity for each pier, forces in in the wall at that level, Vwx, shall be S. distributed to each pier, Vp, in proportion to PDD/H. For each pier at that level: Va >_ Vr........ (46-19) and for the wall at that level: Vwx <_7-Vr.......... (46-20) (2) Non -rocking Mode. Where at least one pier at a level is incapable of sustaining a rocking mode, i.e., the pier shear capacity is less than the pier rocking shear capacity, forces in the wall at that level, Vwx, shall be distributed to each pier,Vp, in proportion to D/H, such that Vwx = 7VP. For at least one pier at that level: Va < Vr............ (46-21) For each pier at that level: Vp <_ Va........... (46-22) and Vp <_ Vr........... (46-23) If Vp >Vr in one or more piers, omit such piers from the analysis and repeat the procedure for the remaining piers or strengthen and reanalyze the wall. (iii) Masonry Pier Tension Stress. Unreinforced masonry wall piers need not be analyzed for tension stress. C. Shear Walls Without Openings. Shear walls without openings shall be analyzed as for walls with openings except that Vr shall be calculated as follows: Vr = (0.50PD + 0.25Pw)D/H ....................(46-24) 2. Plywood sheathed shear walls. Plywood sheathed shear walls may be used to resist lateral loads for buildings with flexible diaphragms analyzed according to provisions of Section III (c). Plywood sheathed shear walls may not be used to share lateral loads with other materials along the same line of resistance. 3. Combinations of Vertical Elements. A. Lateral Force Distribution. Lateral forces shall be distributed among the 9. vertical resisting elements in proportion to their relative rigidities, except that moment frames shall comply with Section A2346(e)3B. B. Moment Resisting Frames. A moment frame shall not be used with a URM wall in a single line of resistance unless the wall has piers that are capable of sustaining rocking in accordance with III (e)1B and the frames are designed to carry 100% of the lateral forces. 10. DETAILED SYSTEM DESIGN REQUIREMENTS SECTION IV ( a ) General. (b) Wall Anchorage. 1. Anchor Locations. All unreinforced masonry walls shall be anchored at the roof and floor levels as required in Section III (c)2. Ceilings with substantial rigidity and abutting masonry walls shall be connected to walls with tension bolts at a maximum anchor spacing of 6 feet. Ceiling systems with substantial mass shall be braced at the.perimeter to diaphragms. 2. Anchor Requirements. Anchors shall be tension bolts through the wall as specified in Table No. D- or by an approved equivalent at a maximum anchor spacing of 6 feet. All existing wall anchors shall be secured to the joists to develop the required forces. The Building Official may require testing to verify the adequacy of the embedded ends of existing wall anchors. 3. Minimum Wall Anchorage. Anchorage of masonry walls to each floor or roof shall resist a minimum force determined by Section 2312(g)2 of the Building Code or 200 pounds per linear foot, whichever is greater, acting normal to the wall at the level of the floor or roof. Existing wall anchors, installed under previous permits, must meet or must be upgraded to meet the requirements of this Chapter. 4. Anchors at Corners. At the roof and all floor levels, both shear and tension anchors shall be provided within two feet horizontally from the inside of the corners of the walls. 5. Anchors with Limited Access. When access to the exterior face of the masonry wall is prevented by proximity of an existing building, wall anchors conforming to Item 5b in Table D may be used. (c) Collectors. Collector elements shall be provided which are capable of transferring the seismic forces originating in other portions of the building to the element providing the resistance to those forces. (d) Ties and Continuity. Ties and continuity shall conform to Section 2312(h)2E. (e) Wall Bracing. 1. General. Where a wall height -thickness ratio exceeds the specified limits, the wall may be laterally supported by vertical bracing members per Section IV (e)2 or by reducing the wall height by bracing per Section IV (e)3. 2. Vertical Bracing Members. Vertical bracing members shall be attached to floor and roof construction for their design loads - .._ 1].. independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one-half the unsupported height of the wall nor 10 feet. Deflection of such bracing members at design loads shall not exceed one-tenth of the wall thickness. 3. Wall Height Bracing. The wall height may be reduced' by bracing elements connected to the floor or roof. Horizontal spacing of the bracing elements and wall anchors shall be as required by design but shall not exceed 6 feet on center. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by the vertical displacement of the floor or roof. (f) Parapets. Parapets and exterior wall appendages not conforming to this Chapter shall be removed, or stabilized or braced to ensure that the parapets and appendages remain in their original position. The maximum height of an unbraced unreinforced masonry parapet above the lower of either the level of tension anchors or roof sheathing, shall not exceed one and one-half (1-1/2) times the thickness of the parapet wall. If the required parapet height exceeds this maximum height, a bracing system designed for the force factors specified in Table 23-P of the Building Code for walls shall support the top of the parapet. Parapet corrective work must be performed in conjunction with the installation of tension roof anchors. The minimum height of a parapet above the wall anchor shall be twelve (12) inches. EXCEPTION: If a reinforced concrete beam is provided at the top of the wall, the minimum height above the wall anchor may be six (6) inches. (g) Veneer. 1. Unreinforced masonry walls which carry no design loads other than their own weight may be considered as veneer if they are adequately anchored to new supporting elements. 2. Veneer shall be anchored with approved anchor ties, conforming to the required design capacity specified in the Building Code and placed at a maximum spacing of 24 inches with a maximum supported area of two (2) square feet. EXCEPTION: Existing veneer anchor ties may be acceptable provided the ties are in good condition and conform to the following minimum size, maximum spacing and material requirements. Existing veneer anchor ties shall iron strips not less than one inch in length and one -sixteenth of an 8" X 1/16") or equal and shall be be corrugated galvanized in width, eight inches inch in thickness (1" X located and laid in �:... _ . 12. every alternate course in the vertical height of the wall at a spacing not to exceed 17 inches on centers horizontally. As an alternate, such ties may be laid in every fourth course vertically at a spacing not to exceed nine (9) inches on centers horizontally. 3. The location and condition of existing veneer anchor ties shall be verified as follows: A. An approved testing laboratory shall verify the location and spacing of the ties and shall submit a report to the Building Official for approval as a part of the structural analysis. B. The veneer in a selected area shall be removed to expose a representative sample of ties (not less than four) for inspection by the Building Official. (h) Truss and Beam Supports. Where trusses and beams other than rafters or joists are supported on masonry, independent secondary columns shall be installed to support vertical loads of the roof or floor members. The loads shall be transmitted down to adequate support. (i) Adjacent Buildings. 1. Where elements of adjacent buildings, do not have a separation of 5 inches, the allowable height/thickness ratios for "buildings with crosswalls" per Table B shall not be used in the direction of consideration. 2. Where buildings do not have a separation of at least 5 inches and the diaphragm levels of the adjoining structures differ by more than one and one-half time the wall thickness, supplemental vertical gravity load carrying members shall be added to support the loads normally carried by the wall and such members shall not be attached to the wall. The loads shall be transmitted down to the foundation. 13. TABLE HORIZONTAL CONFIGURATION OF MATERIALS NO. A FORCE FACTOR C CP Roofs with straight or diagonal 0.5 sheathing and roofing applied directly to the sheathing, or floors with straight tongue and groove sheathing. Diaphragms with double or multiple layers of boards 0.75 with edges offset and blocked plywood systems. 14. TABLE NO. $_ ALLOWABLE VALUE OF HEIGHT -THICKNESS RATIO OF UNREINFORCED MASONRY WALLS Seismic Zone 3 Seismic Zone 4 Seismic Zone 4 Wall Types Buildings Buildings with All Other Crosswallsl Buildinas Walls of one-story 16 buildings First -story wall 18 of multi -story building Walls in top story 14 of multi -story buildings All other walls 16 162,3 13 16 15 1423 9 16 13 lApplies to the Special Procedures of Section III (d) only. See Section III (d)7 for other restrictions. 2This value of height -to -thickness ratio may be used only where mortar shear tests establish a tested mortar shear strength, vt, of not less than 100 psi or where the tested mortar shear strength, vt, is not less than 60 psi and a visual examination of the collar joint indicates not less than 50% mortar coverage. 3Where a visual examination of the collar joint indicates not less than 50% mortar coverage and the tested mortar shear strength, vt, is greater than 30 psi but less than 60 psi, the allowable -height -to - thickness ratio may be determined by linear interpolation between the larger and smaller ratios in direct proportion to the tested mortar shear strength, vt. 15. TABLE NO. C. - ALLOWABLE ALLOWABLE VALUES FOR EXISTING MATERIALS EXISTING MATERIALS OR CON- FIGURATIONS OF MATERIALS) ALLOWABLE VALUES 1. HORIZONTAL DIAPHRAMS4 a. Roofs with straight 100 lbs. per foot sheathing and roofing for seismic shear applied directly to the sheathing. b. Roofs with diagonal 250 lbs. per foot sheathing and roofing for seismic shear applied directly to the sheathing. c. Floors with straight 100 lbs. per foot tongue -and -groove for seismic shear sheathing. d. Floors with straight 500 lbs. per foot sheathing and finished for seismic shear wood flooring with board edges offset or perpendicular. e. Floors with diagonal 600 lbs. per foot sheathing and finished for seismic shear wood flooring. 2. CROSSWALLS2,4 a. Plaster on wood or metal Per side: 200 lbs. lath per foot for seismic shear b. Plaster on gypsum lath 175 lbs. per foot for seismic shear C. Gypsum wall board, 75 lbs. per foot unblocked edges for seismic shear d. Gypsum wall board, 125 lbs. per foot blocked edges for seismic shear 16. TABLE NO.0 . ALLOWABLE VALUES FOR EXISTING MATERIALS (Cont.) EXISTING MATERIALS OR CON- FIGURATIONS OF MATERIALS1 ALLOWABLE VALUES4 3. EXISTING FOOTINGS, WOOD FRAMING, STRUCTURAL STEEL, -AND REINFORCED STEEL a. Plain concrete footings b. Douglas fir wood. C. Reinforcing steel. d. Structural Steel. f'c = 1500 psi unless otherwise shown by tests Allowable stress same as No. 1 D.F.3 ft = 18,000 lbs. per square inch maximum.3 ft =20,000 lbs. per square inch maximum.3 1Material must be sound and in good condition. 2Shear values of these materials may be combined, except the total combined value shall not exceed 300 lbs. per foot. 3Stresses given may be increased for combinations of loads as specified in Section 71"' 4A one-third increase in allowable stress is not allowed. 17. N w 4 540-----1---�--r---�-------t------r--� --� 480 420 _-- L• -1---1-- --1-- '_--L--1---+_-� ' � 1 -1 1 � 1 � 1 - �-- ' 1• 360 T - - - ' -----� -; -�- 1 300--T•--•�--�-----,-------+--------,---1 � ,♦ 1 1 � 1 � 1 , I , 1 ---r--1 �-1--J- -t---L--r-- L- --r---+---t---t. t , ♦ t , 1 1 � 1 , 1 , 1 240 ---+•--1--♦ --'-----'-----1---+-----�---' � , 1 ♦, 1 1 t 1 , 1 , 1 180---L--'----�--L ' -�--' --1-- '---'---' - - -� - - r- - - 1 - - 1 ,O' 120 - - -'- - 1 -' - 1 - ' 1 - t - t - ---T--+--n---+---,-� ---r-- ----+---,---1. 1(D2' 60 _--t--1---1--,---j-----r--1----J---1---1 -----1---+---'---:-- L ----1--� -1---1 O 0 1 FIGURE N0. 1 2 3 4 5 6 Demand -Capacity Ratio, DCR - ACCEPTABLE DIAPHRAGM SPAN 1. TABLE NO. D4 ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION NEW MATERIALS OR CONFIGURATIONS OF MATERIALS ALLOWABLE VALUES4 HORIZONTAL DIAPHAGMS Plywood sheathing applied directly over existing straight sheathing with ends of plywood sheets bearing on joists or rafters and edges of plywood located on center of individual sheathing boards. CROSSWALLS a. Plywood sheathing applied directly over wood studs. No value shall be given to plywood applied over existing plaster or wood sheathing. b. Drywall or plaster applied directly over wood studs. c. Drywall or plaster applied to sheathing over existing wood studs. 225 lbs. per foot 1.33 times the value specified in Table No. 25-K-1 Uniform Building Code for shear walls. 100 percent of the values in Table No. 47-I of the Uniform Building Code. 50 percent of the values plywood specified in Table No. 47-I of the Uniform Building Code. 19. TABLE No. D4 ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION (continued) NEW MATERIALS OR CONFIGURATIONS OF MATERIALS ALLOWABLE VALUES4 4. TENSION BOLTS Bolts extending entirely 1800 lbs. per bolt. through unreinforced masonry walls secured 900 lbs. for 2 wythe with bearing plates on far side walls. of a 3 wythe minimum wall with at least 30 square inches of area .2► 3 5. SHEAR BOLTS Bolts embedded a 133 percent of the minimum of 8 inches into values for plain unreinforced masonry walls. masonry specified for Bolts shall be centered in solid masonry in 2-1/2 inch -diameter hole with Tables No. 24-E of the dry -pack or non -shrink grout Uniform Building around circumference of bolt.1,3 Code. No values larger than those given for 3/4 inch bolts shall be used. 6. COMBINED TENSION AND SHEAR BOLTS a. Through Bolts - Combined Shear and Tension Bolts meeting the above requirements Tension: Same as for for tension bolts and shear bolts1,2,3 tension bolts Shear: Same as for shear bolts b. Embedded Bolts - Combined Shear and Ten_ion Bolts extending to the exterior face of the wall with a 2 1/2 inch round plate under the head and drilled at an angle of 22-1/2 degrees -to the horizontal. Installed as specified for shear bolts. 1, 2,3 Tension: Same as for tension bolts Shear: Same as for shear bolts N 7. TABLE NO. D4 ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION (continued) NEW MATERIALS OR CONFIGURATION OF MATERIALS ALLOWABLE VALUES4 INFILLED WALLS Reinforced masonry infilled openings in existing unrein- forced masonry walls. Provide keys or dowels to match rein- forcing. 8. REINFORCED MASONRY Masonry piers and walls rein- forced per Chapter 24. 9. REINFORCED CONCRETE Concrete footings, walls and piers reinforced as specified in Chapter 26 of the Uniform Building Code and designed for tributary loads. 1Bolts to be tested 2Bolts to be 1/2 -inch minimum in diameter. Same as values specified for unrein- forced masonry walls. Same as values specified in Section 2409. Same as values specified in Chapter 26 of the Uniform Chapter Building Code. 3Drilling for bolts and dowels shall be done with an electric rotary drill. Impact tools shall not be used for drilling holes or tightening anchors and shear bolt nuts. 4A one-third increase in allowable stress is not allowed. 21. DEFINITI%- 3, SYMBOLS, & NOTATIONS DEFINITIONS: For the purposes of these ipegulations applicable definitions in the Building Code shall also apply. COLLAR JOINT is the vertical space between adjacent wythes and may contain mortar. CROSSWALL is a wall that meets the requirements of Section A2346(d)3. A crosswall is not a shear wall. CROSSWALL SHEAR CAPACITY is the length of the crosswall times the allowable shear value, vcLo. DIAPHRAGM EDGE is the intersection of the horizontal diaphragm and a shear wall. DIAPHRAGM SHEAR CAPACITY is the depth of the diaphragm times the allowable shear value, vuD. FLEXIBLE DIAPHRAGM is a diaphragm of wood construction or other construction of similar flexibility. NORMAL WALL is a wall perpendicular to the direction of seismic forces. OPEN FRONT is an exterior wall plane without vertical elements in one or more stories which resist the required lateral forces. POINTING is the partial reconstruction of the bed joints of a URM wall as defined in UBC Standard No. 24-42. UNREINFORCED MASONRY (URM) WALL is a masonry wall in which the area of reinforcing steel is less than 25 percent of that required by the Building Code for reinforced masonry. UNREINFORCED MASONRY BEARING WALL. A URM wall which provides the vertical support for a floor or roof for which the total superimposed load is over 100 pounds per linear foot of wall. YIELD STORY DRIFT is the lateral displacement of one level relative to the level above or below at which yield stress is first developed in a frame member. Symbols and Notations. For the purposes of these regulations the applicable symbols and definitions in the Building Code shall also apply. A = Area of unreinforced masonry pier, square inches. 22. Ab = Area of the bed joints above and below the test specimen for each in-place shear test. C Numerical coefficient as specified in Section 2312(g) and given in Table 23-P of the Building Code and Table A•_- of this Chapter.. D = In -plane width dimension of pier, inches, or depth of diaphragm, feet. DCR - Demand -capacity ratio specified in Section III (d), Fwx = Force applied to a wall at level x, pounds. H = Least clear height of opening on either side of pier, inches. h/t = Height/thickness ratio of URM wall. Height h is measured between wall anchorage levels. L = Span of diaphragm between shear walls, or span between shear wall and open front, feet. Lo = Length of crosswall, feet. Li = Effective span for an open front building specified in Section III (d)8, feet. PD = Superimposed dead load at the top of the pier under consideration, pounds. PD+L = Actual dead plus live load in place at the time of testing, pounds. PW = Weight of wall, pounds. Va = vaA, the allowable shear in any URM pier, pounds. Vcb = Total shear capacity of crosswalls in the direction of analysis immediately below the diaphragm level being investigated, JvcLo, pounds. Vca = Total shear capacity of crosswalls in the direction of analysis immediately above the diaphragm level being investigated, EvcLo, pounds. Vr = 0.5PD(D/H), the rocking shear of any URM wall or wall pier, pounds. Vwx = Total shear force resisted by a shear wall at the 23. level under consideration, pounds. Vp Shear force assigned to a pier on the basis of its relative shear rigidity, pounds. Vs = Shear force assigned to a spandrel on the basis of the shear forces in the adjacent wall piers and tributary dead plus live loads. Vtest Load in pounds at incipient cracking for each in- place shear test per UBC Standard 23-40. va = Allowable shear stress for unreinforced masonry,psi. vc = Allowable shear value for a crosswall sheathed with any of the materials given in Tables C or DS pounds per foot. vt = Mortar shear strength vto = Mortar shear test values vu = Allowable shear value for a diaphragm sheathed with any of the materials given in Tables C or D, pounds per foot. IvuD = Sum of diaphragm shear capacities of both ends of the diaphragm. 17-vuD = For diaphragms coupled with crosswalls 7-7-vuD includes the sum of shear capacities of both ends of diaphragms coupled at and above the level under consideration. Wd = Total dead load tributary to a diaphragm, pounds. IWd = Total dead load tributary to all of the diaphragms at and above the level under consideration, pounds. Ww = Total dead load of an unreinforced masonry wall above the level under consideration or above an open front of a building, pounds. Wwx = Dead load of a URM wall assigned to Level x halfway above and below the level under consideration. 24.